Low Voltage Products

Huatech Low Voltage Products Full Series

Related products

 
 
Technical Parameter Unit LiTEK Series Miniature Circuit Breaker (MCB) MeTEK7 Series Moulded Case Circuit Breaker (MCCB) WeTEK7 Series Air Circuit Breaker (ACB)
Product Type - Miniature Circuit Breaker (MCB) Moulded Case Circuit Breaker (MCCB) Air Circuit Breaker (ACB)
Applicable Standard - IEC 60898, GB Standard IEC 60947-2, GB/T 14048.2 IEC 60947-2, GB/T 14048.1
Rated Working Voltage (Ue) V 230/400 AC 400, 415, 690 AC 400, 415, 690, 1140 AC
Rated Working Current (In) A 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 10 ~ 800 400 ~ 6300
Ultimate Short-Circuit Breaking Capacity (Icu) A/kA N-type: 6000
 
H-type: 10000
25 ~ 70 kA 55 ~ 100 kA
Service Short-Circuit Breaking Capacity (Ics) k - 25 ~ 70 kA (Ics = Icu) 55 ~ 100 kA
Rated Impulse Withstand Voltage kV 6 8 12
Current Limiting Class - Class 3 - -
Pole Number P 1/2/3/4 3/4 3/4
Main Functions - Short-circuit protection, Overload protection, Isolation, Control Power distribution protection, Motor protection Measurement, Diagnosis, Communication, Selective protection, Power monitoring
Mechanical Endurance Times 20000 Long service life Long service life
Electrical Endurance Times 10000 Long service life Long service life
Operating Temperature Range °C -35 ~ +70 Working: -35 ~ +70
 
(24h average ≤ 35)
 
Storage: -40 ~ +75
Working: -40 ~ +60
 
(24h average ≤ 35)
Maximum Altitude for Use m ≤ 2000 ≤ 2000 ≤ 2000
Pollution Degree - - Class 3 Class 3
Humidity Resistance - Class 2 (RH 95% @ 55°C) RH ≤ 50% @ 40°C; RH ≤ 90% @ 20°C RH ≤ 50% @ 40°C; RH ≤ 90% @ 20°C
Installation Method - DIN rail mounting Vertical (≤±22.5°), Horizontal Fixed type / Draw-out type
 
Horizontal / Vertical wiring
Terminal Type - Tunnel terminal - -
Terminal Wiring Capacity mm² 1~32A: ≤25
 
40~63A: ≤35
- -
Rated Torque N·m N-type (1~32A): 2.5
 
N-type (40~63A): 3.0
 
H-type (1~63A): 3.0
- -
Trip Unit Types - - Thermal-magnetic, Electromagnetic, Electronic Intelligent trip unit, Undervoltage trip, Shunt trip
Optional Accessories - OF Auxiliary Contact, SD Alarm Contact, MX Shunt Release Various modular accessories Communication interface
Structural Features - Compact, Quick closing Wide adaptability, Maintenance-free No arcing distance, Compact structure

 