Primary Power Distribution
Huatech Primary Power Distribution Full Series
Related products
| No. | Parameter | Unit | VEP Indoor Solid-Encapsulated Vacuum Circuit Breaker | VEP-M Indoor Solid-Encapsulated Vacuum Circuit Breaker | FEP Indoor SF₆ Circuit Breaker | VFS Indoor Generator Circuit Breaker | VEC Vacuum Contactor-Fuse Combination Unit |
|---|---|---|---|---|---|---|---|
| 1 | Rated Voltage | kV | 12 / 17.5 / 24 / 40.5 | 12 | 12 / 40.5 | 12 | 7.2 / 12 |
| 2 | Rated Frequency | Hz | 50 (17.5kV: 50/60) | 50 | 50 | 50 | 50 |
| 3 | Power Frequency Withstand Voltage (Auxiliary Circuit) | kV | 2 | 2 | 2 | - | - |
| 4 | 1min Power Frequency Withstand Voltage
|
kV | 12kV:42
|
42 | 12kV:42
|
42 | 7.2kV:32
|
| 5 | 1min Power Frequency Withstand Voltage
|
kV | - | - | 12kV:48
|
50 | - |
| 6 | Lightning Impulse Withstand Voltage (Peak)
|
kV | 12kV:75
|
75 | 12kV:75
|
75 | 7.2kV:60
|
| 7 | Lightning Impulse Withstand Voltage (Peak)
|
kV | - | - | 12kV:85
|
85 | - |
| 8 | Partial Discharge | pC | - | - | ≤5 | - | - |
| 9 | Rated Normal Current | A | 630~5000* | 630~4000* | 1250~3150* | 1250~5000* | Contactor: 400
|
| 10 | Rated Short-Circuit Breaking Current | kA | 20 / 25 / 31.5 / 40 / 50 | 20 / 25 / 31.5 / 40 | 12kV:31.5
|
40 / 50 | Contactor: 4 |
| 11 | Rated Short-Time Withstand Current | kA | 20 / 25 / 31.5 / 40 / 50 | 20 / 25 / 31.5 / 40 | 12kV:31.5
|
40 / 50 | 4 (4s) |
| 12 | Rated Short-Circuit Making Current (Peak) | kA | 50 / 63 / 80 / 100(125) / 125(150) | 50 / 63 / 80 / 100 | 12kV:31.5
|
115 / 140 | Contactor: 4
|
| 13 | Rated Peak Withstand Current | kA | 50 / 63 / 80 / 100(125) / 125(150) | 50 / 63 / 80 / 100 | 12kV:80
|
- | - |
| 14 | Rated Out-of-Phase Breaking Current | kA | - | - | 12kV:7.9
|
- | - |
| 15 | Rated Earth Fault Breaking Current | kA | - | - | 12kV:27.4
|
- | - |
| 16 | Rated Back-to-Back Capacitor Bank Breaking Current | A | - | - | 1250 | - | - |
| 17 | Rated Cable Charging Breaking Current | A | - | - | 12kV:25
|
- | - |
| 18 | Rated Short-Circuit Duration | s | 12/17.5/40.5kV:4
|
4 | 4 | 4 | - |
| 19 | DC Component of Rated Short-Circuit Breaking Current | % | - | - | - | ≥80 | - |
| 20 | Operation Times (Short-Circuit Breaking) | Times | - | - | - | 10 | - |
| 21 | Operation Times (Load Current Breaking) | Times | - | - | - | 50 | - |
| 22 | Max. Short-Circuit Breaking Current (Combination Unit) | kA | - | - | - | - | 50 |
| 23 | Operating Frequency | Times | - | - | - | - | Mechanical Latch: 300,000
|
| 24 | Operating Voltage | V | - | - | - | - | DC110, DC220, AC110, AC220 |