ComPacT NS 630-3200A High Current Series

Schneider Molded Case Circuit Breaker ComPacT new generation Full Series.

Related products

 
 
Item Content
Frame Current (AF Rating) Two frame specifications:
 
1. NS630b~NS1600 (1600AF)
 
2. NS1600b~NS3200 (3200AF)
Rated Current In Adjustable rated current range: 630A / 800A / 1000A / 1250A / 1600A / 2000A / 2500A / 3200A
Pole Options Standard:3P,4P; mainstream 3P3D / 4P3D configuration, neutral pole optional with full/half protection design
Ultimate Breaking Capacity Icu@415V AC • NS630b~1600: N(50kA)/H(70kA)/S(150kA)/L(200kA)
 
• NS1600b~3200: H(70kA)/M(85kA)
Trip Unit Types (All MicroLogic Electronic Only, no thermal-magnetic type) 1.MicroLogic2.0/2.0E: L(overload)+I(instantaneous short-circuit), basic distribution protection
 
2.MicroLogic5.0/5.0E: LSI(overload+short-time+instantaneous), selective cascade protection
 
3.MicroLogic6.0/6.0E: LSIG+earth fault protection
 
4.MicroLogic7.0: LSIG+integrated residual current protection+full power metering(I/U/P/E/cosφ/freq)
Mounting Mode 1.Fixed type: available for all frame sizes
 
2.Withdrawable(Draw-out) type: optional for NS630b~3200 full series; plug-in structure not supported for this high-current NS range
Connection Termination 1.Front flat connection(FCF): factory standard
 
2.Rear horizontal(RCTH) / Rear vertical(RCTV): optional rear wiring
 
3.Cable lug terminal for Cu/Al cable; dedicated busbar connection optional for large current cabinet
Rated Operational Voltage Ue AC230/400/415/690V,50/60Hz; Ui=1000V, Uimp=12kV

 

  • toolbar